15.3.4. Other Commands Used During Data Release
The following commands are often used during command driven
data release. For a complete listing of all available commands,
please refer to Section 18.
1.
Site ID:
To send the Site ID, type
^B03
[Enter]
.
2.
Display Current Alarm Record:
Type
^B08
[Enter]
.
3.
Remaining Memory Space:
To send a message that lists
NetLink's remaining memory, type
^B21
[Enter]
.
4.
Set-Up Switches:
To send a message that lists the current
status of the Set-Up Switches, type
^B24
[Enter]
.
5.
Number of Stored Records:
To send a message that lists
the number of records in the current memory partition, type
^B20
and press
[Enter]
.
6.
Display Separator Line:
To send a line of dashes, which
can be used to visually separate downloaded data, type
^B26
and press
[Enter]
.
7.
Continuous Binary Block Read:
To initiate a continuous
binary block read, invoke command ^B07. Blocks are sent
continuously, without acknowledgment, and cannot be
retransmitted during the current read session. Data is sent
in binary block format, regardless of the current output
mode setting. All data type and source port arguments are
available. For more information, please refer to Section 18.
Note:
Command ^B07 (Continuous Binary Block
Read) should not be used while the Auto Delete
function is enabled. If ^B07 is invoked while Auto
Delete is enabled, NetLink will erase data without
waiting for the polling device to acknowledge
reception.
8.
Binary Information Block:
To send a status information
block in binary format, type
^B73
and press
[Enter]
. The
information block includes the Site ID, current time and
date, Reason for Action, Partition Record Count, and
Percent Full. This information is sent in binary block
format, regardless of the current output mode setting.
Responses to all of the above commands end with
<Carriage Return><Line Feed>.
15-13
Buffer Functions (Polling)