8.2.1.
Default Alarm Filter Actions
Alarm Action parameters determine how NetLink will react when
an alarm is generated. The Default Alarm Filter Actions select
parameters that are applied to all newly defined Alarm Clues.
This allows the user to assign identical actions to a series of clues
without manually entering parameters for each clue.
Notes:
·
Definition of the Default Alarm Filter Action
parameters is optional.
·
Default Alarm Action parameters are
only
applied
to newly defined Alarm Clues. These defaults will
not be applied to PBX Inactivity Alarms, the 80%
Full Alarm, or the Input Contact Alarm.
·
When new Alarm Clues are defined, the default
values can be altered or eliminated, as discussed in
Section 8.5.1.
The following Default Alarm Action Parameters are available.
8.
Action:
Specifies the default action that will be performed
when an alarm is generated. The available options are
None, Callout, Alphanumeric Page, Numeric Page, SNMP
Trap, Output Contact, and Console. For more information,
please refer to Section 12.
9.
Phone Number:
The default number that will be dialed
when an Alarm Clue generates a callout or page action.
Note:
For Numeric Paging, this prompt can specify
both the Pager phone number and a numeric
"message". In this case, the phone number is entered
in the following format:
"
PHONENO@MESSAGENO#
"
Where "
PHONENO
" is the pager phone number, and
"
MESSAGENO
" is any user-selected number that will
notify the receiver that an alarm has occurred. For
example, to dial 555-1212 and send the message
"111", the phone number would be defined as
"
5551212@111#
".
8-4
PollCat NetLink User's Guide
Содержание PollCat NetLink
Страница 2: ......
Страница 20: ...3 8 PollCat NetLink User s Guide...
Страница 74: ...6 24 PollCat NetLink User s Guide...
Страница 140: ...14 6 PollCat NetLink User s Guide...
Страница 255: ......
Страница 256: ...5 Sterling Irvine California 92618 949 586 9950 Toll Free 1 800 854 7226 Fax 949 583 9514 http www wti com...