Protective Elements
Parameter
Description
Setting range
Default
Menu path
t
Tripping delay
0.00 - 300.00s
0.00s
[Protection Para
/<1..4>
/V-Prot
/VG[1]]
Meas Circuit
Superv
Activates the use of the measuring circuit supervision.
In this case the module will be blocked if a measuring
circuit supervision module (e.g. LOP, VTS) signals a
disturbed measuring circuit (e.g. caused by a fuse
failure).
inactive,
active
inactive
[Protection Para
/<1..4>
/V-Prot
/VG[1]]
Residual Voltage Supervision Module Input States
Name
Description
Assignment via
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/V-Prot
/VG[1]]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/V-Prot
/VG[1]]
ExBlo TripCmd-I
Module input state: External Blocking of the Trip Command
[Protection Para
/Global Prot Para
/V-Prot
/VG[1]]
Residual Voltage Supervision Module Signals (Output States)
Signal
Description
active
Signal: active
ExBlo
Signal: External Blocking
Blo TripCmd
Signal: Trip Command blocked
ExBlo TripCmd
Signal: External Blocking of the Trip Command
Alarm
Signal: Alarm Residual Voltage Supervision-stage
Trip
Signal: Trip
TripCmd
Signal: Trip Command
397
MRU4
DOK-HB-MRU4-2E