Supervision
Direct Commands of the CBF
Parameter
Description
Setting range
Default
Menu path
Res Lockout
Reset Lockout
inactive,
active
inactive
[Operation
/Reset]
Setting Group Parameters of the CBF
In order to prevent a faulty activation of the BF Module, the pickup (alarm)
time must be greater than the sum of:
Operating time of the protective relay
+The close-open time of the breaker (please refer to the technical data of
the manufacturer of the breaker);
+Drop off time (current- or position indicators)
+Security margin.
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/Supervision
/CBF]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/Supervision
/CBF]
t-CBF
If the delay time is expired, an CBF alarm is given out.
0.00 - 10.00s
0.20s
[Protection Para
/<1..4>
/Supervision
/CBF]