Protective Elements
Commissioning: External Protection
Object to be tested
Test of the module External Protection
Necessary means
Depending on the application
Procedure
Simulate the functionality of the External Protection (Alarm, Trip, Blockings...) by (de-)energizing of the digital
inputs.
Successful test result
All external alarms, external trips and external blockings are correctly recognized and processed by the device.
504
MRU4
DOK-HB-MRU4-2E