Supervision
Setting Group Parameters of the Voltage Transformer Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/Supervision
/VTS]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/Supervision
/VTS]
ΔV
In order to prevent faulty tripping of phase selective
protection functions that use the voltage as tripping
criterion. If the difference of the residual voltage and
the calculated value V0 is higher than the pick up value
ΔV, an alarm event effected after the excitation time. In
such a case, the existence of a fuse failure, a broken
wire or a faulty measuring circuit can be assumed.
0.20 - 1.00Vn
0.50Vn
[Protection Para
/<1..4>
/Supervision
/VTS]
Alarm delay
Alarm delay
0.1 - 9999.0s
1.0s
[Protection Para
/<1..4>
/Supervision
/VTS]
536
MRU4
DOK-HB-MRU4-2E