Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Scale Factor 27
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 27
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value 28
Analog value can be used to report values to the
master (DNP)
1..n, TrendRecList -.-
[Device Para
/DNP3
/Point map
/Analog Input]
Scale Factor 28
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 28
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value 29
Analog value can be used to report values to the
master (DNP)
1..n, TrendRecList -.-
[Device Para
/DNP3
/Point map
/Analog Input]
249
MRU4
DOK-HB-MRU4-2E