Protective Elements
f - Frequency [81O/U, 78, 81R]
Available elements:
f[1] ,f[2] ,f[3] ,f[4] ,f[5] ,f[6]
All frequency protective elements are identically structured.
Frequency - Measuring Principle
The frequency is calculated as the average of the measured values of the
three phase frequencies. Only valid measured frequency values are taken
into account. If a phase voltage is no longer measurable, this phase will be
excluded from the calculation of the average value.
The measuring principle of the frequency supervision is based in general on the time measurement of complete
cycles, whereby a new measurement is started at each zero passage. The influence of harmonics on the measuring
result is thus minimized.
Frequency tripping is sometimes not desired by low measured voltages which for instance occur during alternator
acceleration. All frequency supervision functions are blocked if the voltage is lower 0.15 times Vn.
400