Technical Data
Voltage and Residual Voltage Measurement
The following Technical Data are valid for 8-pole (large) voltage measurement terminals.
Nominal voltages:
60 - 520 V (can be configured)
Max. measuring range:
800 V AC
Continuous loading capacity:
800 V AC
Power consumption:
at Vn = 100 V S = 22 mVA
at Vn = 110 V S = 25 mVA
at Vn = 230 V S = 110 mVA
at Vn = 400 V S = 330 mVA
Frequency range:
50 Hz or 60 Hz
±
10%
Terminals:
Screw-type terminals
Frequency Measurement
Nominal frequencies:
50 Hz / 60 Hz