Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Assignment 7
Assignment
1..n, Assignment
List
-.-
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Inverting 7
Inverting of the state of the assigned signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Operating Mode
Operating Mode
Working current
principle,
Closed-circuit prin-
ciple
Working current
principle
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
t-hold
To clearly identify the state transition of a binary output
relay, the "new state" is being hold, at least for the
duration of the hold time.
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
t-Off Delay
Switch Off Delay
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
Latched
Defines whether the Relay Output will be latched when
it picks up.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
Acknowledgement Acknowledgement Signal - An acknowledgement signal
(that acknowledges the corresponding binary output
relay) can be assigned to each output relay. The
acknowledgement-signal is only effective if the
parameter "Latched" is set to active.
Only available if: Latched = active
1..n, Assignment
List
-.-
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
Inverting
Inverting of the Binary Output Relay.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
Assignment 1
Assignment
1..n, Assignment
List
Prot.Alarm
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
83
MRU4
DOK-HB-MRU4-2E
Содержание High PROTEC MRU4
Страница 1: ...Manual Voltage Relay MRU4 Software Version 3 0 b DOK HB MRU4 2E Revision B English...
Страница 51: ...Installation and Connection Ethernet RJ45 Terminals 51 MRU4 DOK HB MRU4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 64: ...Navigation Operation Navigation Operation 64 MRU4 DOK HB MRU4 2E 1 2 3 5 7 6 8 10 9...