Technical Data
Time Synchronization IRIG
Nominal input voltage:
5 V
Connection:
Screw-type terminals (twisted pair)
RS485*
Master/Slave:
Slave
Connection:
9-pole D-Sub socket
(external terminating resistors/in D-Sub)
or 6 screw-clamping terminals RM 3.5 mm (138 MIL)
(terminating resistors internal)
In case that the RS485 interface is realized via terminals, the
communication cable has to be shielded.
Fibre Optic*
Master/Slave:
Slave
Connection:
ST-Plug
Wavelength
820 nm
Optical Fast Ethernet*
Connection:
LC-Plug
Wavelength:
1300 nm
Fiber:
62.5/125 or 50/125 µm multimode
URTD-Interface*
Connection:
Versatile Link
*availability depends on device
Boot phase
After switching on the power supply the protection will be available in approximately 8 seconds. After approximately
65 seconds the boot phase is completed (HMI and Communication initialized).