Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Scale Factor 3
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 3
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value 4
Analog value can be used to report values to the
master (DNP)
1..n, TrendRecList -.-
[Device Para
/DNP3
/Point map
/Analog Input]
Scale Factor 4
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 4
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value 5
Analog value can be used to report values to the
master (DNP)
1..n, TrendRecList -.-
[Device Para
/DNP3
/Point map
/Analog Input]
237
MRU4
DOK-HB-MRU4-2E