Protective Elements
Device Planning Parameters of the Low-Voltage-Ride-Through
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
do not use
[Device planning]
Setting Group Parameters of the Low-Voltage-Ride-Through
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/General settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/General settings]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/General settings]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/General settings]
Measuring Mode
Measuring/Supervision Mode: Determines if the phase-
to-phase or phase-to-earth voltages are to be
supervised
Phase to Ground,
Phase to Phase
Phase to Ground [Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/General settings]
483
MRU4
DOK-HB-MRU4-2E