Communication Protocols
Time Synchronization
Time and date of the relay can be set by means of the time synchronization function of the IEC60870-5-103
protocol. If the time synchronization signal is send out with a confirmation request, the device will answer with a
confirmation signal.
Spontaneous Events
The events that are generated by the device will be forwarded to the master with numbers for standard function
types / standard information. The data point list comprises all events that can be generated by the device.
Cyclic Measurement
The device generates on a cyclic base measured values by means of ASDU 9. They can be read out via a class 2
query. Please take into account that the measured values will be send out as multiples (1.2 or 2.4 times the rated
value). How to set 1.2 or 2.4 as multiplier for a value can be taken from the data point list.
The parameter “Transm priv meas val” defines if additional measurement values should be transmitted in the private
part. Public and private measured values are transmitted by ASDU9. That means that either a “private” or a “public”
ASDU9 will be transmitted. If this parameter is set, the ASDU9 will contain additional measured values that are an
enhancement of the standard. The “private” ASDU9 is send with a fixed function type and information number that
does not depend the type of device. Please refer to the data point list.
Commands
The data point list comprises a list of the supported commands. Any command will be responded by the device with
a positive or negative confirmation. If the command is executable, the execution with the corresponding reason for
the transmission (COT) will be lead in at first, and subsequently the execution will be confirmed with COT1 within a
ASDU9.
Disturbance Recording
The disturbances recorded by the device can be read out by means described in standard IEC60870-5-103. The
device is in compliance with the VDEW-Control System by transmission of an ASDU 23 without disturbance records
at the beginning of an GI-Cycle.
A disturbance record contains the following information:
Analog Measured Values, IL1, IL2, IL3, IN, Voltages VL1, VL2, VL3, VEN;
Binary States, transmitted as marks, e.g. Alarms and Trips.
The Transmission ratio will not be supported. The transmission ratio is included in the “Multiplier”.
Blocking the Transmission Direction
The relay does not support functions to block the transmission in a certain direction (supervision direction).
205
MRU4
DOK-HB-MRU4-2E
Содержание High PROTEC MRU4
Страница 1: ...Manual Voltage Relay MRU4 Software Version 3 0 b DOK HB MRU4 2E Revision B English...
Страница 51: ...Installation and Connection Ethernet RJ45 Terminals 51 MRU4 DOK HB MRU4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 64: ...Navigation Operation Navigation Operation 64 MRU4 DOK HB MRU4 2E 1 2 3 5 7 6 8 10 9...