Protective Elements
Setting Group Parameters of the Reconnection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/General settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/General settings]
Meas Circuit
Superv
Activates the use of the measuring circuit supervision.
In this case the module will be blocked if a measuring
circuit supervision module (e.g. LOP, VTS) signals a
disturbed measuring circuit (e.g. caused by a fuse
failure).
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/General settings]
V Ext Release PCC
Fc
Activate the release signal of the Point of Common
Coupling. The line-to-line voltage is greater than 95%
of VN.
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/General settings]
Reconnect.
Release Cond
This signal indicates that the mains voltage is
recovered.
V Internal Release,
V Ext Release PCC
V Internal
Release
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/Release Para]
PCC Fuse Fail VT
Fk
Blocking if the fuse of a voltage transformer has tripped
at the PCC.
Only available if: Reconnect. Release Cond = V Ext
Release PCC
inactive,
active
inactive
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/Release Para]
VLL> Release
Minimum voltage (line-to-line) for reclosure
(Restoration Voltage)
Only available if: Reconnect. Release Cond = V
Internal Release
0.70 - 1.00Vn
0.95Vn
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/Release Para]
474
MRU4
DOK-HB-MRU4-2E
Содержание High PROTEC MRU4
Страница 1: ...Manual Voltage Relay MRU4 Software Version 3 0 b DOK HB MRU4 2E Revision B English...
Страница 51: ...Installation and Connection Ethernet RJ45 Terminals 51 MRU4 DOK HB MRU4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 64: ...Navigation Operation Navigation Operation 64 MRU4 DOK HB MRU4 2E 1 2 3 5 7 6 8 10 9...