Protective Elements
Parameter
Description
Setting range
Default
Menu path
VLL< Release
Maximum voltage (line-to-line) for reclosure
(Restoration Voltage)
Only available if: Reconnect. Release Cond = V
Internal Release
1.00 - 1.50Vn
1.10Vn
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/Release Para]
f<
Lower frequency limit for the reclosure (Restoration
Voltage)
40.00 - 69.90Hz
47.5Hz
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/Release Para]
f>
Upper frequency limit for the reclosure
40.00 - 69.90Hz
50.05Hz
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/Release Para]
t-Release Blo
Time stage (delay) for the reclosure of the energy
resources. The Mains seddle time takes based on
exirience approx. 10 - 15 minutes.
0.00 - 3600.00s
600s
[Protection Para
/<1..4>
/Intercon-Prot
/ReCon
/Release Para]
475
MRU4
DOK-HB-MRU4-2E