Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Nom voltage
Nominal voltage of the digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
Inverting 3
Inverting the input signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
Debouncing time 3 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
no debouncing
time,
20 ms,
50 ms,
100 ms
no debouncing
time
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
Inverting 4
Inverting the input signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
Debouncing time 4 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
no debouncing
time,
20 ms,
50 ms,
100 ms
no debouncing
time
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
Inverting 5
Inverting the input signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
Debouncing time 5 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
no debouncing
time,
20 ms,
50 ms,
100 ms
no debouncing
time
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
Inverting 6
Inverting the input signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
73
MRU4
DOK-HB-MRU4-2E
Содержание High PROTEC MRU4
Страница 1: ...Manual Voltage Relay MRU4 Software Version 3 0 b DOK HB MRU4 2E Revision B English...
Страница 51: ...Installation and Connection Ethernet RJ45 Terminals 51 MRU4 DOK HB MRU4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 64: ...Navigation Operation Navigation Operation 64 MRU4 DOK HB MRU4 2E 1 2 3 5 7 6 8 10 9...