Installation and Connection
Profibus DP via D-SUB
D-SUB
Electro-mechanical assignment
The connection cable must be shielded. The shielding has to be fixed at the
screw which is marked with the ground symbol at the back side of the
device.
Profibus DP/ Modbus
®
RTU / IEC 60870-5-103 via fibre optic
Fibre Optic
Ethernet / TCP/IP via Fiber Optics
Fiber Optics - FO
62
MRU4
DOK-HB-MRU4-2E
D-SUB assignment - bushing
1 Earthing/shielding
3 RxD TxD - P: High-Level
4 RTS-signal
5 DGND: Ground, neg. Potential of aux voltage supply
6 VP: pos. Potential of the aux voltage supply
8 RxD TxD - N: Low-Level
5
1
9
6