Protective Elements
Synchrocheck Override Conditions
If enabled the following conditions can override the synchrocheck function:
•
LBDL = Live Bus – Dead Line
•
DBLL = Dead Bus – Live Line
•
DBDL = Dead Bus – Dead Line
Also the synchrocheck function can be bypassed by an external source.
When the synchrocheck function is overridden or bypassed,
synchronization has to be secured by other synchronizing systems before
breaker closing!
439
MRU4
DOK-HB-MRU4-2E
Содержание High PROTEC MRU4
Страница 1: ...Manual Voltage Relay MRU4 Software Version 3 0 b DOK HB MRU4 2E Revision B English...
Страница 51: ...Installation and Connection Ethernet RJ45 Terminals 51 MRU4 DOK HB MRU4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 64: ...Navigation Operation Navigation Operation 64 MRU4 DOK HB MRU4 2E 1 2 3 5 7 6 8 10 9...