Product Description

L

Z45FK, Z46FK, Z47FK, Z60FK Coupling Relays

Application

These coupling relays are used to control plant components in the DDC 
system. They serve as switching coupling components between the DDC 
switching outputs and the device inputs; they can be used to control valve 
actuators, pumps, burners or fans, for example.
These coupling relays are fitted with spring terminals which make it 
possible to connect wires quickly and easily. It is not necessary to use a 
tool to connect solid wires and litz wires with conductor end sleeves; an 
ordinary screwdriver is sufficient to connect litz wires without conductor 
end sleeves.
Connected wires can be quickly disconnected again with a screwdriver. 
Terminal slots provided for the A1 and A2 connections enable the simple 
and quick connection of up to 10 analog encoders or coupling relays 
through connecting bridges (Z43).

Content

Page

Important Information on Product Safety ...............................................................................................................2
Item........................................................................................................................................................................3

Technical data .....................................................................................................................................................3
Accessories (not included in delivery) .................................................................................................................3
Dimensions ..........................................................................................................................................................4
Connection...........................................................................................................................................................4

Mounting and Installation.......................................................................................................................................5

Cable connection .................................................................................................................................................6

Connection example with input-output modules ....................................................................................................8

Содержание Z45FK

Страница 1: ...are fitted with spring terminals which make it possible to connect wires quickly and easily It is not necessary to use a tool to connect solid wires and litz wires with conductor end sleeves an ordina...

Страница 2: ...mmissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recogn...

Страница 3: ...es Z46FK 2 000 000 switching cycles Display LED operating display Manual switch Z45FK Z46FK None Z47FK Manual switch at field level Z60FK Manual switch at field level with a poten tial free feedback c...

Страница 4: ...05 Dimensions Connection ZxxFK Z43 250 V AC 6 A 1500 VA 11 A1 14 12 GN A2 Z45FK 14 24 12 22 11 A1 21 230 VAC 0 25 A 60 VA GN A2 Z46FK A1 A3 0 ON A3 AUTO OFF 11 A1 12 14 250 V AC 6 A 1500 VA GN A2 Z47F...

Страница 5: ...c installation can cause death due to electric shock Mounting removal may only be carried out when power is switched off Comply with VDE guidelines and local wiring regulations when mounting removing...

Страница 6: ...any further and it clicks into place in the spring terminal In the case of litz wires without conductor end sleeves the spring terminal must be opened using a slotted screwdriver Insert the screwdrive...

Страница 7: ...oper place to make the cut Then insert the connecting bridge Z43 from the top or from the bottom into the contact slot and press it down WARNING Contact with live components of the building s electric...

Страница 8: ...are switched at the output terminals In secondary earthed systems PELV this prevents any unwanted connection to ground or the reference potential and prevents an active signal from being generated at...

Отзывы: