Cable connection
■
Disconnect unit from power supply.
■
Strip the insulation from 10 mm of the wire. Cross-sectional area of
connection:
Solid wire 0.08 .. 2.5 mm²
Litz wire without conductor end sleeve 0.08 .. 2.5 mm² Litz wire with conductor
end sleeve 0.5 .. 1.5 mm²
Solid wires and litz wires with conductor end sleeves can be inserted into the
spring terminals (1) directly. Insert the wire straight and press it in until the wire
will not go any further and it clicks into place in the spring terminal.
In the case of litz wires without conductor end sleeves, the spring terminal must
be opened using a slotted screwdriver. Insert the screwdriver into the test
socket (2) under the contact in order to open it, insert the litz wire straight, and
then remove the screwdriver.
■
"Terminal slot (3) for Z43 connecting bridge.
■
"Device connection - see wiring diagram.
Removing a Wire
Insert a slotted screwdriver (max. blade width 3 mm) into the
test socket (2) under the contact to open the spring
terminal (1), then remove the wire.
Removing the Module from the Standard Rail
Gently press in the spring under the module with a slotted
screwdriver and remove the module upward.