WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013
TECH-477/D.W.O. 21424
Page 98 of 206
store the values according to its data type (MM/DD/YY HH:MM:SS), so
the year is just a two digits number.
9.3.2.9 LCD Contrast, Serial Number, Revision
A subdirectory of Parameters/Transducer, it has a group of parameters to set the clock,
LCD contrast, device’s serial and revision information.
Time and Date: Current date from RTC (TIME_AND_DATE parameter). Write in
this parameter to adjust the RTC.
The DTM will display the time and date format according to what
is defined on Windows (see time and date format configurations
in Windows Control Panel in order to change it). Setting a new
TIME_AND_DATE value must follow the same format, otherwise,
the DTM will reject it.
Independent to what's defined in Windows settings, the device
will store the values according to its data type (MM/DD/YY
HH:MM:SS), so the year is just a two digits number.
LCD Contrast: Changes the contrast of the LCD, The range is [26, 63].
This contrast will be use when the electronic temperature is
between -5ºC and 60ºC.
If the electronic temperature is equal or below -5ºC the contrast
will be set automatically to 63.
If the electronic temperature is equal or above 60ºC the contrast
will be set automatically to 26.
WSN Password: Password to enable to change the serial number
WSN Control Flag: This flag will inform if the serial number was changed properly.
WSN Serial
Number:
Show the current serial number. To write a new value, the
password in the WSN Password parameter must be correct.
Revision ID: Firmware revision identification.
Revision Date: Firmware revision release date.