Step 2.
Press fit the inner beacon to the inner beacon coupler. The inner beacon needs to
be properly oriented. Use the symbols on the top of the inner beacon to mount as shown in
Condition 1 or Condition 2. (See Figure 5-2). Condition 1 and Condition 2 show the
placement of the inner beacon with respect to the positioner housing while the actuator is in
the fail position.
Step 3.
Mount the positioner to the bracket. As stated in Step 2 make sure that the
positioner is mounted in a fashion that properly orients it with respect to the inner beacon.
Condition 1:
Actuator fails in a clockwise direction.
Spring Return
Output Port 2 is plugged
Output Port 1 is piped to turn the actuator counter
clockwise
Double Acting
Output Port 2 is piped to turn the actuator clockwise
Output Port 1 is piped to turn the actuator counter
clockwise
Placed at 6:00
II
Placed at 3:00
Condition 2:
Actuator fails in a counter clockwise
direction.
Spring Return
Output Port 2 is plugged
Output Port 1 is piped to turn the actuator clockwise
Double Acting
Output Port 2 is piped to turn the actuator counter
clockwise
Output Port 1 is piped to turn the actuator clockwise
Placed at 9:00
II
Placed at 6:00
Figure 5-2