- No reaction of the field device;
- ARM;
- Self-calibration;
- Hall sensor gain calibration;
- Low position calibration;
- High position calibration;
- Transducer calibration;
- Servo PID tuning.
Transducer Command State: Current calibration state.
Enable Alert: This parameter can be used to enable the available
alerts separately.
Alert Status: Shows the alerts enable that is ON in the moment.
Reset Counters: This parameter will reset all counters used for alert
or reset each counter separately.
Total Travel Deadband: In units of TRAVEL_COUNT, this parameter will
setup a dead band to assume that the valve is
totally open or totally close to be used by the
TOTAL_TRAVEL_COUNT. Change this value will
change the values of TRAVEL_LIMIT_LOW and
TRAVEL_LIMIT_UP.
Travel Count Unit: Units used to show the TRAVEL_COUNT.
Travel Count: Counter the total valve movement. The unit is
defined in the TRAVEL_COUNT_UNITS.
Travel Count Deadband: The minimum movement to increase the
TRAVEL_COUNT. The unit is defined in the
TRAVEL_COUNT_UNITS.
Travel Count Limit: Travel limit to indicate the TRAVEL_CNTR alert.
The unit is defined in the TRAVEL_COUNT_UNITS.
Internal Temperature Min: Minimum temperature to start the indication of
TEMP_MAX_MIN alert.
Internal Temperature Max: Maximum temperature to start the indication of
TEMP_MAX_MIN alert.
Setpoint Deviation: Maximum valve position deviation from setpoint.
Setpoint Deviation Deadband: Dead band of the maximum valve position deviation
from setpoint.
Setpoint Deviation Timeout: Timeout to start a setpoint deviation alert indication.
POSITION_HI Alert: Highest position to start the POSITION_HI alert
indication. The dead band for this parameter is the
TOTAL_TRAVEL_DB.
POSITION_LO Alert: Smallest position to start the POSITION_LO alert
indication. The dead band for this parameter is the
TOTAL_TRAVEL_DB.
Fault State Value: If the POSITIONING_VALUE status is bad and the
FAULT_STATE_OPTION is set to
FAULT_STATE_VALVE then parameter TRD_SP
will be set to this value.