WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013
TECH-477/D.W.O. 21424
Page 14 of 206
IEC 61000-6-4:2006 Electromagnetic
compatibility (EMC) – Emission
standard for industrial environments
IEC 61326-2:2005 Electrical equipment
for measurement, control and laboratory
use - EMC requirements
3 Order Guide
The ICoT PA positioner is designed to handle a wide range of control valve applications. Please use the
following ordering guide to help choose the ICoT positioner that best suits the application.
ICoT 5500 (ICoT PA) Positioner Ordering Guide
INTELLIGENT POSITIONERS PROFIBUS PA
ICoT 5500
SEE BELOW FOR HAZARDOUS RATINGS
Base Model
55 PROFIBUS PA
Actuator Type
1 Linear* (Free magnet assy. Include up to 2-1/2” stroke; strokes>2-1/2”, consult factory)
3 Rotary
Mounting Style
0 Direct Mount (ICoT mounted on actuator)
5 Remote Mount (ICoT mounted remote from actuator)
7 NAMUR Mount (order with stainless NAMUR mounting kit separately)
8 Mod Mount (for Tyco MRP and 79U actuators only; supplied with mounting kit)
Hazardous Rating
NI Non-incendive (Class I, Div. 2, Groups A, B, C, D Class II, Div. 2, Groups F, G)
IS Intrinsically Safe (Class I, Div. 1 & 2, Groups A, B, C, D Class II, Div. 1, Groups E, F, G with approved I.S. barrier)
AI Intrinsically Safe – ATEX EX ia IIC T4 approved
II Intrinsically Safe – IEC Ex ia IIC T4 approved
Housing Material
E Engineered Resin
S 316 Stainless Steel (Not listed for Hazardous Rating. Pending Approvals) (Mounting Style 0 & 5 only)
A Aluminum (Not listed for Hazardous Rating. Pending Approvals) (Mounting Style 0 & 5 only)
Supply Pressure
H High Pressure (40-120 psi)
L Low Pressure (15-45 psi)
V High Flow (40-120 psi, for larger actuators)
S Super High Flow (40 – 120 psi, 5.5 CV)
Calibration/Communication
P 3-button on-board keypad & PROFIBUS PA Protocol
Conduit Entry
A One 1/2" NPT (F)
B One M20 (F)
Limit Switch Options
0 None
2
Two SPST hermetically Sealed switches** (NOT available w/ Mounting Style 7 or 8)
Position Transmitter Output
A None
Pneumatic connections
N 1/4” NPT (3/8” NPT with High Flow Option)
B 1/4” BSP (3/8” BSP with High Flow Option)
F 1/4” NPT w/ Filter-Regulator Assembly (3/8” NPT with High Flow Option)
55 3 5 IS E H P A 2 A N = Model Number
5535ISEHPA2AN
* Linear valve stroke and fail position must be specified at time of quotation.
** Not available with “Linear” Actuators type or “Remote Mounting Style”