Compact Class B.
Profile Revision: 3.02 – ICoT is compatible with profile 3.02
Execution Time: Parameter is reserved for future use and contains
no relevant data.
Number of Parameters: Number of used indices (parameters of a block
including the non-implemented optional parameters.
Index of VIEW 1: The index of the View 1.
Number of View Lists: Number of view lists defined in a block.
General
Static Revision No.: The revision level of the static data associated with
the block. The Static Revision No. is changed by the
device each time data are written to the static
parameter.
TAG: Physical device tag.
Strategy: The strategy field can be used to help group blocks.
Alert Key: The alert parameter (0 – 255) has a user-assigned
value which may be used in sorting alarms or
events generated by a block.
Block Modes
Target Mode: Sets the desired mode for the block. The input
parameters of the block in conjunction with the state
of the block are used to determine if the block can
achieve the requested target mode. The automatic
modes used in this profile are Auto and RCAS. The
manual modes are LO and Man. In O/S mode, the
normal algorithm is no longer executed.
Actual Mode: Indicates the current mode of operation the block is
able to achieve.
Permitted Mode: Defines the modes which are allowed in this
instance of the block.
Normal Mode: The mode which the block uses during normal
operation conditions.
Alarm Summary
Current State Alarm Sum: The alarm sum of the current alarm state.
Unacknowledged State Alarm
Sum:
The alarm sum of the unacknowledged alarm state.
Unreported Stated Alarm Sum: Unreported State Alarm Sum.
Disabled State Alarm Sum: Disabled State Alarm Sum.