18 Appendix H - Controlling the ICoT PA Position using the
Proficore Ultra Interface, ProfiCaptain software
1. First we need to add the GSD file. If the
GSD file was added before skip to step 6.
2. From the ProfiTrace main dialog, press the
tab ProfiCaptain.
3. From the ProfiCaptain, select the option
Settings -> Add/Copy GSD to catalog into
the upper menu bar and choose the right
GSD file (WLC0E88.GSD).
4. Answer yes to generate a new catalog.
5.
Now if you check the GSD catalog in the
right, you will be able to see the device.
6. Connect the Proficore Ultra interface in the
Computer USB port.
7. From ProfiTrace tab click over
"Init
ProfiCore Ultra".
8.
Because the Proficore Ultra is not
connect in any other master. You will
see that it was not able to auto detect
the baud rate.
9. Select the baud rate supported by the
coupler we are using.