Configuration Options
LCD & Key Menu
Transducer Block Parameter
From DTM
RTC
Stro
Adjs
WORKING_SP
C
TRD Servo PID manual tuning directory - SP
D
Op
WORKING_SP=100
C
TRD Servo PID manual tuning directory - SP
(Value=100)
D
Cls
WORKING_SP=0
C
TRD Servo PID manual tuning directory - SP
(Value=0)
D
Notes: A – Must be preceded by XD_COMMAND=8 (Arm command)
B – Must be preceded by TRD COMMANDS=Arm
C – Transducer MODE_BLK must be at 0x10 (Manual)
D – Transducer Mode must be in Man
8.3.8.2 General Device Parameters
Some general device parameters are also available for viewing in the Transducer Block
Table 8-5
General Device Parameters
Parameter
Description
Final Value
(POSITIONING_VALUE)
The target valve position as written by the Analog Output
block
Final Position Value
(FEEDBACK_VALUE)
The actual measured valve position
Pressure Port A
(PRESSURE_A)
This displays the air pressure from port A of the manifold
(as a percentage of the air pressure measured during
calibration)
Internal Temperature
(INTERNAL_TEMP)
The ICoT PA module internal temperature as measured by
an on-board temperature sensor (°C)
8.3.8.3 Complete list of parameters of the Transducer Block
Table 8-6
Relative
Index
Parameter Name
Description
Default
Value
Read/
Write
0 BLOCK_OBJECT
The
BLOCK_OBJECT
parameter is the first
parameter of every block. It
contains the characteristics
of the block e.g. block type
and profile number.
-
r
1
ST_REV
A block has static block
parameters that are not
changed by the process.
Values are assigned to these
parameters during the
configuration or optimization.
0 r