16 Appendix E - Grounding Schematic
1
CONNECTION FROM DP/PA COUPLER TO POSITIONER IS 0.8
mm
2
MBP TYPE A CABLE
(BELDEN 3079A OR EQUIVALENT)
MAXIMUM DISTANCE 1900 METERS OR 6200 FEET.
2
SHIELD SHALL BE CONNECTED TO GROUND AT ONE POINT
ONLY IN ORDER TO AVOID GROUND LOOPS AND NOISE
INTERFERENCE.
3
THE FOLLOWING TABLE, PER IEC61158, INDICATES THE
MINIMUM DISTANCE BETWEEN CABLE TRAYS AND CONCUITS
CONTAINING LEVEL 1, AND 64VDC, 25VAC < 450VAC OR
>450VAC.
PROFIBUS
PA
60VDC OR 25<450
VAC
60VDC OR 25<450
VAC
Any cable subject to
ray exposure
PROFIBUS PA 10
CM
20CM
50CM
60VDC OR 25<450
VAC
10 CM
10 CM
50 CM
> 450 VAC
20 CM
10 CM
50CM
Any cable subject to
ray exposure
50 CM
50 CM
50 CM