WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013
TECH-477/D.W.O. 21424
Page 58 of 206
8.3.8.1 Configuration Option Parameters
Many of the configuration option available on the local LCD & pushbutton menu are also
available over the Fieldbus network by changing parameters in the Transducer Block (see
table below).
Table 8-4
Configuration Options
LCD & Key Menu
Transducer Block Parameter
From DTM
ACAL
PID Auto
SELF_CALIB_COMMAND=2
A
XD_COMMAND=9
A
TRD Calibration directory - TRD Command=SELF
Calibration
B
MCAL
Lo
XD_COMMAND=11
A
TRD Calibration directory - TRD Command=Low
position calibration
B
Hi
XD_COMMAND=12
A
TRD Calibration directory – TRD Command=High
position calibration
B
PID
PID Auto
XD_COMMAND=14
A
TRD Calibration directory – TRD Command=Servo PID
Tuning
B
Man P
SERVO_GAIN_1 (0.0-255.0)
TRD Servo PID manual tuning directory – Proportional
Action 1 (0.0-255.0)
Man I
SERVO_RESET_1 (0.0-255.0)
TRD Servo PID manual tuning directory – Integral
Action 1 (0.0-255.0)
Man D
SERVO_RATE_1 (0.0-255.0)
TRD Servo PID manual tuning directory – Derivative
Action 1 (0.0-255.0)
Snsr
XD_COMMAND=10
A
TRD Calibration directory - TRD Command=HALL
Sensor gain calibration
B
Trnd
XD_COMMAND=13
A
TRD Calibration directory - TRD Command=
Transducer calibration
B
Cofg
Flow
LIN_TYPE
TRD Basic Setup Group directory – Flow Type=no
linearization or linearization table or Equal Percentage
or Quick Opening
Type
VALVE_TYPE (0=Rot, 1=Lin)
TRD Basic Setup Group directory – Valve Type=linear
moving valve, sliding valve or rotary moving valve,
part-turn
Flop
FLOP (0,1)
TRD Basic Setup Group directory – Display mode=Off
or On
OPSP
VALVE_OPEN_SLEW_LIMIT (1-5) TRD Slew Rate Setup Group directory – Opening
Speed Limit=
-
slowest - 20% Dynamic Speed
-
slow - 40% Dynamic Speed
-
normal - 60% Dynamic Speed
-
fast - 80% Dynamic Speed
-
fasted - 100% Dynamic Speed
-
custom – speed defined by Travel Time Open
CLSP
VALVE_CLOSE_SLEW_LIMIT (1-5) TRD Slew Rate Setup Group directory – Closing
Speed Limit=
-
slowest - 20% Dynamic Speed
-
slow - 40% Dynamic Speed
-
normal - 60% Dynamic Speed
-
fast - 80% Dynamic Speed
-
fasted - 100% Dynamic Speed
-
custom – speed defined by Travel Time Close
EDb
SP_DEVIATION_DB
TRD Alert Group directory - Setpoint Deviation Dead
band
LCD