Read Reference Curve: This option will read the reference curve, reference measured
break time and reference time interval from the device.
Read Last curve: This option will read the curve points, measured break time and time
interval related with the last FST.
Result Stroke Test:
Result of last FST. Valid values:
no result: test running
success: test finished with no error
reference store: reference data was successful saved
fail-break time exceeded: the device exceed the break time limit,
defined by Break Timeout, to start the movement,
Fail stroke test time exceeded: the device exceed the time limit to
execute the full stroke test.
Aborted by external reason: the FST was not started because the
valve is not full open.
Fail no supply pressure: the FST was not started because there
is not air pressure at supply port.
10.6 PA Profile – Block View
Here is possible to view all function block parameters. They are dividing by function
block.