10.4.1 Process
Variables
Located at first tab of Process Variable && Trend curves, this tab displays, in a form of a
bar graph, all the measured values by the device's sensors.
SP: Setpoint - Process variable from the analog output block
Working SP: Process variable from the analog output block after
characterization, FLOP and reverse acting (SIGNAL_ACTION) in
POSITION_UNITS
Feedback: The actual position of the final control element in units defined in
the POSITION_UNITS parameter.
Pressure Port A: Pressure of manifold output port A - It is located in the port A. Its
unit is defined in the PRESSURE_UNITS.
The accuracy over the span is ± 2% between 0 - 50ºC.
The offset has a variation of 3.5% for each 1ºC of variation.
If the unit is %, then 100% is the maximum pressure used in the
calibration.