38.
Click on "Save Watch List" to save
these entries.
39. To change the setpoint using this tool, we
need first set a good status. Click on
“Modify to” column at sp.status line and
type 128 (0x80) and press ENTER (the
status was sent to device). The device will
show PA-CTR indicating the setpoint is
been update through AO channel.
40. Now setting a new setpoint.
Click on
“Modify to” column at sp.value line and
type a value, for instance, 50 and press
ENTER (the setpoint was sent to device).
We will be able to see the setpoint at
device LCD.