manualshive.com logo in svg
background image

IP80-TFI03GB-B 

Installation and Maintenance Manual

IP8000-0##-# / IP8100-0##-# 
Electropneumatic Positioner

1 Safety Instructions

This manual contains essential information for the protection of users
and others from possible injury and/or equipment damage.

Read this manual before using the product, to ensure correct handling,
and read the manuals of related apparatus before use.

Keep this manual in a safe place for future reference.

These instructions indicate the level of potential hazard by label of
"DANGER", "WARNING" or "CAUTION", followed by important safety
information which must be carefully followed.

To ensure safety of personnel and equipment the safety instructions in
this manual and the product catalogue must be observed, along with
other relevant safety practices.

WARNING

• The compatibility of pneumatic equipment is the responsibility of

the person who designs the pneumatic system or decides its
specifications.

Since the products specified here can be used in various operating 
conditions, their compatibility with the specific pneumatic system must
be based on specifications or after analysis and/or tests to meet 
specific requirements.

• Only trained personnel should operate pneumatically operated

machinery and equipment.

Compressed air can be dangerous if an operator is unfamiliar with it.
Assembly, handling or repair of pneumatic systems should be 
performed by trained and experienced personnel.

• Do not service machinery/equipment or attempt to remove 

components until safety is confirmed.

1) Inspection and maintenance of machinery/equipment should only

be performed after confirmation of safe locked-out control positions.

2) When equipment is to be removed, confirm the safety process as

mentioned above. Switch off air and electrical supplies and exhaust
all residual compressed air in the system.

3) Before machinery/equipment is re-started, ensure all safety

measures to prevent sudden movement of cylinders etc.
(Supply air into the system gradually to create back pressure, i.e.
incorporate a soft-start valve).

• Do not use this product outside of the specifications.

Contact SMC if it is to be used in any of the following conditions:

1) Conditions and environments beyond the given specifications, or if

the product is to be used outdoors.

2) Installations in conjunction with atomic energy, railway, 

air navigation, vehicles, medical equipment, food and beverage,
recreation equipment, emergency stop circuits, press applications,
or safety equipment.

3) An application which has the possibility of having negative effects on

people, property, or animals, requiring special safety analysis.

CAUTION

Ensure that the air supply system is filtered to 5 microns..

2 Specifications

Protect the unit from impact and dropping during transfer and when
mounted. It may cause failure of the unit.

• Do not use the unit in places with high humidity & temperature. It may

cause malfunctions.

• Do not use this positioner outside of the range of it's specifications as this

can cause failure.

*1 : 1/2 split range is possible with the standard type (by adjusting the span)
*2 : The stroke is adjustable in 0~60° and 0~100°.
*3 : Standard air (JIS B0120): temp.20°C, absolute press. 760mmHg, 

ratio humidity 65%.

2.1 How to Order

3 Installation

WARNING

• Do not install unless the safety instructions have been read and

understood.

• Since zero-point varies depending on the mounting position, the zero point

should be adjusted after installation.

• Avoid hitting the product with metallic objects!
• Avoid using this product in non-explosive environments which can become

explosive due to air leakage!

3.1 Environment

WARNING

• Do not use in an environment where the product is directly exposed to

corrosive gases, chemicals, salt water, water or steam.

• Do not mount the product in a location where it will be subject to strong

vibrations and/or shock.

• Do not mount the product in a location where it is exposed to radiant heat.
• Allow sufficient space for maintenance and adjustment around the product

when mounted.

3.2 Piping

CAUTION

• Before piping make sure to clean away all chips, cutting oil, dust etc.
• When installing piping or fitting into a port, ensure that sealant material

does not enter the port inside. When using seal tape, leave 1.5 to 2 threads
exposed on the end of the pipe/fitting.

3.3 Lubrication

CAUTION

• The positioner has a fixed orifice and nozzle, which contain fine paths in

them. Use filtered, dehydrated air and avoid the use of lubricators as this
may cause malfunction of the positioner. Ensure that the air supply system
is filtered to 5 micron.

Setting

3.4 Handling

CAUTION

• Avoid giving impact to the body and torque motor of the positioner, and

giving excessive force to the armature because this leads to failure. Handle
with care during transport and operation.

• If you leave the positioner at the operation site for a long time without using

it, put the cover on it so that rain water does not enter the positioner. If the
atmosphere is of high temperature or humidity, take measures to avoid
condensation inside. The condensation control measures must be taken
thoroughly for export shipment.

• Avoid setting the positioner near magnetic fields because the

characteristics are effected.

4 Mounting

4.1 Type  IP8000

4.1.1 Example of attaching to actuator

The type IP8000 positioner is compatible with Type IP6000 and IP600 in the
attaching pitch. If you are using IP600 and IP6000 already, the bracket for
these positioner can be used to attach IP8000 to the actuator.

4.2.2 Connection with feedback shaft

4 Mounting (Continued)

4.1.2 Connection with external feedback lever

4.2 Type  IP8100

4.2.1 Example of attaching to actuator

The type IP8000 positioner is compatible with type IP610 and IP6100 in
the attaching pitch. If you are using IP610 or IP6100 already, the bracket
can be used to attach IP8000 to the actuator. If you change from IP6100
to IP8100 and select accessory H (with external scale plate), fork lever
type fitting needs to be adjusted at lower position.

Type

IP8000

IP8100

Lever type lever

Rotary type cam

Item 

Single action 

Double action  Single action  Double action

Input current

4~20mADC (Standard)*

1

Input resistance 

235 

±

15

Ω

Supply air pressure 

0.14~0.7MPa

Standard stroke 

10 ~ 85mm (External 

lever allowable 

runout angle 10

°

~ 30

°

)

Sensitivity

Within 0.1%F S

Within 0.5%F S

Linearity

Within 

± 

1%F S

Within 

± 

2%F S

Hysteresis

Within 0.75%F S

Within 1%F S

Repeatability

Within 

± 

0.5%F S

Thermal coefficient

Within 0.1%F S/

°

C

Output flow rate

80 I/min (ANR) or more (SUP=0.14MPa)*

3

Air consumption

Within 5 I/min (ANR) (SUP=0.14MPa)

Ambient and using 
fluid temperature
Air connection port

Rc1/4 (FEMALE)

Electric wiring 
connection port
Material

Aluminium diecast for the body

Mass

Approx. 2.6kg with terminal box 

(Approx. 2.4kg without terminal box)

Classification of 
degree of protection

60

°

~ 100

°

*

2

-20

°

C ~ 80

°

C

JISF8007 IP65 (conform to IEC pub.529)

G1/2 (FEMALE)

I P 8

00 - 0            -

Q

TYPE

0 LEVER 

TYPE

1 ROTARY 

TYPE

PRESSURE GAUGE
(SUP, OUT1)

0

None

0.2 MPa (R1/8)

0.3 MPa (R1/8)

3

1.0 MPa (R1/8)

CONSTRUCTION

0 NO 

TERMINAL 

BOX

1 WITH 

TERMINAL 

BOX

EMC CERTIFIED

NOTE: WHEN MORE THAN 2 ACCESSORIES
ARE REQUIRED THE SYMBOL SHOULD BE
STATED IN ALPHABETICAL ORDER

ACCESSORIES

NIL NO 

ACCESSORIES 

(WITH STANDARD LEVER)

WITH PILOT VALVE ADDED DIA. 0.7mm
ORIFICE FOR RESTRICTING OUTPUT.

WITH PILOT VALVE ADDED DIA. 1.0mm
ORIFICE FOR RESTRICTING OUTPUT.

C

FORK LEVER ASSEMBLY, TYPE M
(P368010-24)

D

FORK LEVER ASSEMBLY, TYPE S
(P368010-25)

E

WITH LEVER FEEDBACK UNIT FOR
STROKE 35 ~ 100mm, 
(WITHOUT STANDARD LEVER)

F

WITH LEVER FEEDBACK UNIT FOR
STROKE 50 ~ 140mm, 
(WITHOUT STANDARD LEVER)

G

WITH GAIN SUPPRESSION SPRING (A).
(WITHOUT STANDARD GAIN
SUPPRESSION SPRING)

H

WITH EXTERNAL SCALE PLATE UNIT

WITH OPENING CURRENT OUTPUT 
(4-20mA DC)

Positioner

Bracket

Bracket

Positioner

Positioner

Bracket
shape
Example

Bracket
shape
Example

Fig.1 Example of 
directly attaching to
diaphragm valve

Directly attach using the
screw hole at the side of
the positioner and the
screw hole at the yoke side
of the diaphragm valve.

Fig.2 Example of attaching
using the L-shape bracket

Attach by using screw 
hole at the side of the
positioner and the screw
hole at the front mount of
diaphragm valve.

Fig.3 Example of attaching
using front bracket

Attach by using screw 
hole at the back of the
positioner and the screw
hole at the front mount of
diaphragm valve.

Fig.7 Example of attaching using
the positioner back screw

Attaching using the screw hole at
the positioner back and the screw
hole at the actuator top.

Fig.6 Example of attaching using
the positioner side screw

Attaching using the screw hole of a
side of the positioner and the screw
hole at the actuator top.

(1) Attach to the position that the

valve stem and lever form the
right angle when the input
signal is 50% (distribute
evenly with 50% input signal
set as the reference).

(2) Attach to the position of the

runout angle is within the
range of 10° to 30°.

(3) To move the valve stem

downward at the time of input
current increase (normal
actuation), attach to the
position at which the
tightening spring comes to the
upper side of the connecting
metal, as shown in Fig 5.
To move the valve stem
upward (reverse actuation),
turn-over the feedback lever
and attach to the position at
which the tightening spring
comes to the lower side of
connecting metal.

Tighening spring

Right angle

Input 0% (or 100%) position current

Input 100% (or 0%) position current

Input 50% position current

Connecting metal

Valve stem

Positioner body

Fedd back
lever

(The stem moves down as the input increases)

Stem direction

Stem direction

Turn over the feed
back lever

Fig.4 Attaching the feed back lever

OUT1

OUT2

Bracket shape
example

Bracket shape
example

OUT1

OUT2

Fig.5 Use position for feedback lever

(1) Attach to the position at

which the positioner feed
back shaft and the rotary
actuator main shaft are
almost concentric (range in
which the spring pin of feed
back shaft edge enters the
hole of fork lever assembly
shaft edge).

(2) If the seration joint type for

IP610 is made in a special
specification, it can be used 
for this connection.

Fork lever assembly
(P368010-36)

Positionery body

Fork pin unit
(P368010-23)

M8 x 1.25

Actuator main shaft

Spring pin

Fig.8 Attaching the feed back lever

DANGER

In extreme conditions, there is a possibility of 
serious injury or loss of life.

WARNING

If instructions are not followed there is a possibility 
of serious injury or loss of life.

CAUTION

If instructions are not followed there is a possibility 
of injury or equipment damage.

Отзывы: