Connection Type
Table 18: Technical Data
– Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm²
… 2.5 mm², AWG 28 … 14
Stripped lengths
8 mm
… 9 mm / 0.33 in
Table 19: Technical Data
– Power Jumper Contacts
Power jumper contacts
Blade/spring contact, self-cleaning
Table 20: Technical Data
– Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
3.6.9
Climatic Environmental Conditions
Table 21: Technical Data
– Climatic Environmental Conditions
Surrounding air temperature, operation 0
… 55 °C
Surrounding air temperature, storage
−40 … +85 °C
Relative humidity (without
condensation)
Max. 95 %
Operating altitude
0
… 2000 m
Storage altitude
0
… 3000 m
Pollution degree
2
Overvoltage category
II
Protection class
III
Protection type
IP20
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
25 ppm
H
2
S
10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used
in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
Ensure that the connecting cable is correctly dimensioned
The permissible temperature range of the connecting cable must be dimensioned
depending on the mounting position and current intensity because the
temperature of the terminal connection can be up to 24 °C above the expected
surrounding air temperature (at 10 A via the power jumper contacts).