94
Commissioning
WAGO-I/O-SYSTEM 750
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
8.3
Parameterization of the F I/O Module with the
WAGO Parameterization Tool
Check that the parameterization LED is illuminated!
After selecting the F I/O module, check that the F I/O module parameterization
LED is illuminated! A detailed description of indicators is available in Section
“Device Description” > “Indicators”.
Short separation of the sensor supply possible after parameterization!
After the parameterization of the F I/O module, the sensor supply is switched off
for a short moment. This can lead to connected sensors not providing a valid
current value for a short time.
Only qualified persons may perform these tasks!
Adding, exchanging and commissioning F I/O modules may only be carried out
by personnel trained in safety-related procedures!
Check safety functions!
Before commissioning, all safety functions must be checked for their specified
effectiveness!
Depending on the call option, the WAGO Safety Editor is started in either
ONLINE or OFFLINE mode.
Check the set iParameters!
After the parameterization of the F I/O module, the iParameters read back from
the F I/O module must be compared to the expected values and confirmed. The
new iParameters will take effect after the confirmation.
Guard against unauthorized modification of the iParameters!
As stated in EN ISO 13849-1, unauthorized modification of the iParameters must
be prevented. This must be accomplished by a corresponding protection of the
F PLC or the safety application project.