Table 49: Diagnostic Messages
Alarm
Description
Incorrect
F_CRC_Length
Diagnostic
type
Module diagnostics
Coding
0x0045
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The configured F_CRC length cannot be
used in the current operating mode.
Observe the dependency between
F_Par_Version and F_CRC_Length and
select a valid combination.
Classification
Error
Incorrect
F_Par_Version
Diagnostic
type
Module diagnostics
Coding
0x0046
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The set version of the F parameter set is
incorrect. Observe the dependency
between F_Par_Version and
F_CRC_Length and select a valid
combination.
Classification
Error
Internal channel
error
Diagnostic
type
Channel diagnostics
Coding
0x0280
LED indicator
Group error red
Channel status red
Description/
Remedy
The internal hardware test of the F I/O
module failed. If the error occurs
repeatedly after restart, immediately
replace the F I/O module and send it to
WAGO for error analysis.
Classification
Error