124 Diagnostics
WAGO-I/O-SYSTEM 750
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Table 49: Diagnostic Messages
Alarm
Description
Invalid F_CRC1
Diagnostic
type
Module diagnostics
Coding
0x0047
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The F_CRC1 form from the F parameter
set is invalid. Create a consistent
F parameter set.
Classification
Error
Invalid F_Dest_Add
Diagnostic
type
Module diagnostics
Coding
0x0041
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The PROFIsafe address of the F I/O
module must lie within the range of 1 ...
65534. Correct the F parameterization.
Classification
Error
Invalid F parameters
Diagnostic
type
Module diagnostics
Coding
0x0048
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The combination of F parameters is
invalid. Correct the F parameterization.
Classification
Error
Invalid iParameters
Diagnostic type
Module diagnostics
Coding
0x0200
LED indicator
Group error red
Parameterization red, 1 Hz flashing
Description/
Remedy
The iParameter set for the F I/O module is
invalid. Correct the parameterization taking
into account dependencies between
individual settings.
Classification
Error