WAGO-I/O-SYSTEM 750
Diagnostics 131
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
9.6
Firmware Update
Note firmware version!
Only firmware intended for the F I/O module can be loaded.
The system must be checked after a firmware update!
Before commissioning, the safety functions of the automation system must be
checked after changes have been made to the firmware. These tests are a
requirement for occupational safety!
You can update firmware on the Series 750 I/O Modules with the software
“WAGO I/O-Update 750.” The I/O modules can be updated via the service
interface or, for ETHERNET-based fieldbuses, via the fieldbus connection on the
fieldbus coupler/controller.
Observe the following information:
Do Not Switch Off the I/O Module!
Interrupting the update process can damage the I/O module.
Do not remove the I/O module during the update process. Do not interrupt the
power supply!
•
Ensure that communication with the fieldbus coupler/controller is not
interrupted during the update process.
•
Any PLC application running on the controller must be stopped before the
update process.
•
Before an update via the service interface, disconnect the fieldbus cable
from the fieldbus coupler/controller.
•
Do not close the software during the update.
•
Only run the software from a local hard disk.
Additional Information from WAGO Support!
Additional information about the software “WAGO I/O-Update 750” is available
through WAGO Support.