WAGO-I/O-SYSTEM 750
Diagnostics 125
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Table 49: Diagnostic Messages
Alarm
Description
Invalid
F_Source_Add
Diagnostic
type
Module diagnostics
Coding
0x0042
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The PROFIsafe address of the safe
controller must lie within the range of 1 to
65534. Correct the F parameterization.
Classification
Error
Invalid
F_Source_Add
Diagnostic
type
Module diagnostics
Coding
0x0043
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The monitoring time for fail-safe data
exchange must be set to a value greater
than “0 ms”.
Correct the F parameterization.
Classification
Error
Non-supported
F_Block_ID
Diagnostic
type
Module diagnostics
Coding
0x004C
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The F parameter block specified by the
F_Block_ID is not supported by the F I/O
module. Use an F parameter block
supported by the F I/O module.
Classification
Error
Non-supported
F_SIL
Diagnostic
type
Module diagnostics
Coding
0x0044
LED indicator
Group error red
PROFIsafe status red
Description/
Remedy
The F I/O module cannot be operated in
the configured safety integrity level (SIL).
Correct the F parameterization.
Classification
Error