WAGO-I/O-SYSTEM 750
Functions
53
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
4.4
Module- or Channel-Granular Passivation in
PROFIsafe Mode V2.4
The F I/O module is set at the factory so that all input channels are passivated at
the same time in the event of an error. However, it can be configured in such a
way that channel-granular passivation is possible in case of a channel error.
•
Channel-granular passivation
: With this setting, only the affected input
channels are passivated in case of error and all other analog input
channels continue to be used.
•
Module-granular passivation
: With this setting, all input channels are
passivated in case of error.
The settings are made via the “
Passivation Mode
” parameter, which is
described in Section “Commissioning” > … > “Setting Parameters”.
Passivation mode in PROFIsafe Mode V2.4 only!
The parameter is only evaluated if PROFIsafe Mode V2.4 (F_CRC_Seed = 0 and
F_Passivation = 0) is set!
In PROFIsafe Mode V2.6 (F_CRC_Seed = 1 and F_Passivation = 1), this
parameter is ignored and passivated channel granular per RIOforFA.