WAGO-I/O-SYSTEM 750
Diagnostics 127
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Table 49: Diagnostic Messages
Alarm
Description
Overrange 1
Diagnostic
type
Channel diagnostics
Coding
0x0294
LED indicator
Description/
Remedy
The process value of the analog input is in
overrange 1 according to the set data
format.
Check the sensor wiring and the sensor
itself if necessary.
Classification
Warning
Overrange 2
Diagnostic
type
Channel diagnostics
Coding
0x0295
LED indicator
Description/
Remedy
The process value of the analog input is in
overrange 2 according to the set data
format.
Check the sensor wiring and the sensor
itself if necessary.
Classification
Warning
Overrange
F_WD_Time
Diagnostic
type
Module diagnostics
Coding
0x004E
LED indicator
Group error red
PROFIsafe status red, 1 Hz flashing
Description/
Remedy
The time between two data packets from
the safe PLC was greater than the time
set in F_WD_Time. Check the parameter
F_WD_Time and increase the value if
necessary.
Classification
Error