WAGO-I/O-SYSTEM 750
Appendix 151
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Table 57: PROFIsafe F Parameters
F parameters
Default
Value
Description
F_Source_Add
–
The
F_Source_Add
parameter specifies the
PROFIsafe source address. To prevent incorrect
parameterization, the address of the configuration
tool is automatically assigned and cannot be
changed.
The parameter can accept values from 1 to
65534.
The F I/O module only supports address type 1
and does not check the F source address.
F_Dest_Add
–
The
F_Dest_Add
parameter specifies the
PROFIsafe destination address of the F I/O
module. For
F_Dest_Add
, values from 1 to
65534 can be selected.
Each address value may appear in the system
only once. This is checked by the configuration
tool of the safe PLC.
For PROFIsafe communication, the parameter
value must match the PROFIsafe address of the
F I/O module.
The F I/O module only supports PROFIsafe
address type 1!
F_WD_Time
150 ms
The
F_WD_Time
parameter determines the
monitoring time for PROFIsafe communication
between the safe PLC and F I/O module.
At least one valid PROFIsafe telegram must be
exchanged between the safe PLC and the F I/O
module within the monitoring time.
If this condition is not met, the safe PLC or F I/O
module initiates a safe state.
The monitoring time must be selected, so that
telegram execution times are tolerated, but an
interruption in the connection is detected quickly
enough.
The monitoring time can be specified in
increments of 1 ms. The possible value range
(50 ... 10000 ms) is specified by the WAGO
device description file (GSD/GDML).