CANopen option board interface
vacon • 81
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8
Table 101. FB Control Word extension description
8.4.3
FB Speed Reference
Mapped into FB PD in offset 2.
Table 102. FB Speed Reference
Table 103. FB Speed reference description
8.4.4
FB Process data Input 1...8
Mapped into FB PD in offset 3...11.
Table 104. FB Process Data Input 1...8
8.4.5
FB Processdata Input mapping in application
In addition to sending control commands and speed reference values to the application, 8 process
data items can be sent directly to the application to control other features via fieldbus. These can
be, for example, activating preset frequencies, activating or deactivating faults, selecting different
ramp times, controlling I/O's, and so on. Different applications support different features. For more
information, see the application manual. Also, always check the value of the sent data in the appli-
cation manual to see in which format they are given (for example, % values, bit coded values, and
so on).
Table 105. FB Processdata application mapping
Bit
Name
Description
0
1
15
BSTAT2
Bus status
Informs bus status into application
Status of option board
14
BSTAT1
Bus status
Informs bus status into application
13
BFLT
Bus fault
Request fieldbus fault
-
Generate field bus fault
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
FB Speed Reference
Name
Description
Min
Max
FB Speed Reference
Frequency reference at percentage between
minimum and maximum frequency. Control
word DIR bit is used to select rotation direc-
tion.
0
(0%)
10000
(100.00%)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
FB Process data in
PD
Mapped Application Data
Unit
PD in 1
-
-
PD in 2
-
-
PD in 3
-
-
PD in 4
-
-
PD in 5
-
-
PD in 6
-
-
PD in 7
-
-
PD in 8
-
-