vacon • 32
OPTE6 layout and connections
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.2
LED Indications
Figure 8. LED indicators
M = CANopen run led
A = CANopen err led
N = Board status
CANopen run led (green)
CANopen err led (red)
Board status led (green)
LED is
Description
Blinking
The CANopen device is in the pre-operational state.
Single flash
The CANopen device is in the stopped state.
ON
The CANopen device is in the operational state.
LED is
Description
OFF
No error
Blinking
Invalid configuration
Single flash
At least one of the error counters of the CAN controller has
reached or exceeded the warning level (too many error frames).
Double flash
A guard event (NMT slave or NMT master) or a heartbeat event
(heartbeat consumer) has occurred.
Quadruple flash
An expected PDO was not received before the event timer
elapsed.
ON
The CAN controller is bus-off.
LED is
Description
OFF
Option board is not activated.
ON
Option board is in initialization state, waiting activation com-
mand from the AC drive.
Blinking (once/
1s)
Option board is activated and in RUN state. Option board is
ready for external communication.
9339A_00
N A M
M A N
70CVB01605
70CVB01124