CANopen protocol description
vacon • 23
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
3.7.7
0X1014 - COB ID EMCY
The object defines the emergency message COB ID.
Setting MSB (bit 31) to 1 will disable sending of EMCY messages.
3.7.8
0X1016 - Heartbeat Consumer Entries
The device can act as the heartbeat consumer. Up to 8 devices can be monitored, as defined in the
table below. If the heartbeat transmission delay of a defined node ID exceeds the heartbeat time,
the error behaviour is activated according to the error behaviour object.
Table 39: 0x1014 COB ID EMCY
Index
Sub-index
Value
Name
Data type
Access
0x1014
-
0x0
node id
COB ID EMCY
UNSIGNED32
r/w
Table 40: 0x1016 Heartbeat consumer entries
Index
Sub-index
Value
Name
Data type
Access
0x1016
0
0x08
Number of entries
UNSIGNED8
ro
1
0x0000 0000
Consumer heart beat
time 1
UNSIGNED32
r/w
2
0x0000 0000
Consumer heart beat
time 2
UNSIGNED32
r/w
3
0x0000 0000
Consumer heart beat
time 3
UNSIGNED32
r/w
4
0x0000 0000
Consumer heart beat
time 4
UNSIGNED32
r/w
5
0x0000 0000
Consumer heart beat
time 5
UNSIGNED32
r/w
6
0x0000 0000
Consumer heart beat
time 6
UNSIGNED32
r/w
7
0x0000 0000
Consumer heart beat
time 7
UNSIGNED32
r/w
8
0x0000 0000
Consumer heart beat
time 8
UNSIGNED32
r/w
Table 41: Consumer heartbeat time entry
31 24
23 16
15 0
Not used, must be
zeroes.
Node ID
Heartbeat time
Содержание CANopen OPTE6