CANopen option board interface
vacon • 79
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8
8.4
Default process data application mapping
This chapter describes the default mapping of the OPTE6 process data variables to the application
data in the drive. It also provides a description of the application data in the drive. Supported con-
trol/status word bits might differ depending on used application. Please read also the correspond-
ing section of the drive's application manual for additional information.
Table 96. Process data in
Table 94. Transmit PDO Communication Parameter 2
Index
Sub-index
Value
Name
Data type
Access
0x1801
0
6
Highest sub-index
UNSIGNED8
ro
1
0x280 + Node
ID
COB-ID
UNSIGNED32
r/w
2
0xFE
Transmission type
UNSIGNED32
r/w
3
1000
Inhibit time
UNSIGNED16
r/w
4
-
Reserved
UNSIGNED8
ro
5
0
Event timer
UNSIGNED16
r/w
6
0
Sync start value
UNSIGNED8
r/w
Table 95. Transmit PDO Communication Parameter 3
Index
Sub-index
Value
Name
Data type
Access
0x1802
0
6
Highest sub-index
UNSIGNED8
ro
1
0x380 + Node
ID
COB-ID
UNSIGNED32
r/w
2
0xFE
Transmission type
UNSIGNED32
r/w
3
1000
Inhibit time
UNSIGNED16
r/w
4
-
Reserved
UNSIGNED8
ro
5
0
Event timer
UNSIGNED16
r/w
6
0
Sync start value
UNSIGNED8
r/w
Sub-index
Mapped Application data
In Offset0
FB Control word
In Offset 1
FB Control word Extension
In Offset 2
FB Speed reference
In Offset 3
FB Process data in 01
In Offset 4
FB Process data in 02
In Offset 5
FB Process data in 03
In Offset 6
FB Process data in 04
In Offset 7
FB Process data in 05
In Offset 8
FB Process data in 06
In Offset 9
FB Process data in 07
In Offset 10
FB Process data in 08