CANopen protocol description
vacon • 13
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
always the first sub-index on the error field list.
When all active errors are cleared, an empty EMCY
object is transmitted.
If a drive-internal fault occurs, the MSEF field contains the drive fault code. See the application and
user manual for possible fault codes. The ER field holds a bit coded value of the error type. See
object 0x1001 for more details.
Table 14: EMCY message
CAN ID
LENGTH
DATA0
DATA1
DATA2
DATA3
DATA4
DATA5
DATA6
DATA7
0x80 +
Node ID
0x8
EEC
ER
MSEF
Table 15: EMCY message data fields
EEC
Emergency error code
ER
Error register value
MSEF
Manufacturer-specific
error code
Table 16: Used EMCY error codes and description MSEF fields
DATA0
DATA1
DATA2
DATA3
DATA4
DATA5
DATA6
DATA7
0x0000
ER
3: Number of remaining error sources
0x1000
Drive fault codes
0x8110
-
0x8120
-
0x8130
3: Heartbeat consumer subindex
4: Heartbeat consumer node-ID
0x8140
-
0x8210
-
0x8220
-
0x8240
-
0x8250
-
Table 17: Description and behavior of different error situations
EEC
Description
Error behaviour
Err LED
0x0000
Error Reset or No Error
If MSEF field is empty all error sources are cleared and drive
fault is cleared.
-
0x1000
Generic Error
Drive fault codes have changed.
-
0x8120
CAN in Error Passive
Mode
EMCY is sent after CAN driver goes back to active state. This
also clears the fault.
Single flash
0x8130
Life Guard Error
Error is reset when a RTR is received or either of the life
guard objects (0x100C, 0x100D) is written to zero.
Double
flash
Heartbeat Error
Error is reset when a HB message is received by the HB con-
sumer, or the consumer entry is changed (either Node-ID or
Heartbeat Time).