CANopen option board OPTE6 - technical data
vacon • 29
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
4.2.2
Recommended cable
For all OPTE6 installations the use of 4-wire cable is recommended. 4 wires enable the connection
of isolated digital grounds with nodes.
VACON
®
recommends the following cable:
UNITRONIC
®
BUS CAN FD P
Colour-coded in accordance with DIN 47100
Figure 5. Recommended cable
Table 52. Cable thickness, length and baud rate relation
Bit rate
Min cable thickness
1 Mbit/s
0.25
500 kbit/s
0.25
0.34
250 kbit/s
0.25
0.34
0.6
125 kbit/s
0.25
0.34
0.6
100 kbit/s
0.25
0.34
0.6
0.6
50 kbit/s
0.25
0.34
0.6
0.6
Cable
length
25
100
250
500
Содержание CANopen OPTE6