vacon • 68
CANopen option board interface
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
The table below explains the actions taken in different state transitions and which event triggers
which state transition. If the used drive/application does not support different stop bits in Fixed
Control Word, the stop method will always be according to set stop function.
Current state can be determined by reading the value of Statusword data object and comparing the
value of bits to the table below.
Table 64. State transition events and actions
Transition
Event(s)
Action(s)
0
Automatic transition after power-on or reset
Self-initialization is performed
1
Automatic transition after drive status is 'ready'
None
2, 6
Shutdown command
None
3
Switch on command
None
4
Enable operation command
Drive function is enabled
5
Disable operation command
Drive function is disabled
7
Disable voltage or quick stop command
None
8
Shutdown command
Stop by ramp /stop function
9
Disable voltage command
Stop by coast / stop function
10, 12
Disable voltage command
None
11
Quick stop command
Quick stop / stop function
13
Fault signal
Go to fault state and stop by stop
function
14
Automatic transition
None
15
Fault reset command
Reset fault if no fault currently
exists on drive
Table 65. Statusword bits
Bits of the statusword
PDS state
15-8
7
6
5
4
3
2
1
0
x
x
0
x
x
0
0
0
0
Not ready to switch on
x
x
1
x
x
0
0
0
0
Switch on disabled
x
x
0
1
x
0
0
0
1
Ready to switch on
x
x
0
1
x
0
0
1
1
Switched on
x
x
0
1
x
0
1
1
1
Operation enabled
x
x
0
0
x
0
1
1
1
Quick stop active
x
x
0
x
x
1
1
1
1
Fault reaction active
x
x
0
x
x
1
0
0
0
Fault
x = Do not care
Содержание CANopen OPTE6